For example,Бобцов

Plate heat exchangers in absorption lithium bromide thermal transformers

Annotation

Energy efficiency of absorption lithium bromide thermal transformer depends on the depth of heat recovery in solution heat exchanger. In the article shell-and-tube and plate heat exchangers used in the absorption lithium bromide thermal transformers are compared. The appropriate design of plate heat-exchanger prototype with плоскимипластинамиis presented, which is the basis for the development of heat-exchangers with the plates with convex-concave turbulizing surfaces. The evaluation of thermal-hydraulic characteristics of plate heat-exchangers has been made; the efficiency of their using in thermal transformersis shown. The optimum characteristics of the purpose-built plate heat transformersfor Russianabsorption lithium bromide thermal transformerare determined. Forabsorption lithium bromide thermal transformer withone-stage desorption system the recommended channel height of weak solution path in plate heat-exchangeris proved to be not less than 3.0 mm, and forabsorption lithium bromide thermal transformer withtwo-stage desorption system – not less than2.0 mm. ForABHM-1000Vnindustrial refrigerating machine withone-stage desorption the characteristics of the recuperative heat-exchangers current in use and the upcoming ones are compared. It is shown thatwhen using plate heat-exchangers with flate plates refrigerant saving is 15% in relation to the total refrigerant amount loaded into absorption lithium bromide thermal transformer; metal and labour savings for manufacturing absorption lithium bromide thermal transformer in relation to total weight is 5%.

Keywords