Research flow regimes of two-phase refrigerant flow in horizontal pipes
Annotation
The results of experimental studies of flow regimes of two-phase flow of refrigerant R12, R22, R134a in a horizontal pipe inner diameter of 6 mm and 10 mm, with boiling points t0 = -20 ÷ +20˚C, the rate of circulation ω0 = 0,1 ÷ 0,5 m / s. There is generally poor coordination, which can be explained by the authors using the card mode supplies, not the true parameters, which under certain conditions is physically meaningless. The dependence of the boundaries of the flow regime of steam quality, circulation rate, the boiling point, the diameter of the pipe. A comparison of the experimental data with charts Baker (Charge) Hovli, Varma, Maydheyna, Van der Yagta. Found that only 40-50% of the received experimental data are in good agreement with the above diagrams. Studies in addition to the identification of modes also included the study of the true volume steam content by cutoffs.
Keywords
Постоянный URL
Articles in current issue
- Minichannel heat exchangers in refrigerating equipment
- Ecology and calculation of ventilation underground parking
- To leakage calculation in working part of a screw compressor
- Analysis of a thermal condition of the piston compressor stage
- Comparative assessment of annual energy consumption in the central and decentralized air conditioning systems
- The practical use of a KOMDET-M program for piston compressors structural optimization
- Research flow regimes of two-phase refrigerant flow in horizontal pipes
- Innovative methods to improve efficiency existing types of shell-and-tube devices
- Calculation of a line of elasticity perfluoropropane in MATHCAD
- Mobile broadband dampers for vibration plate structure
- Ozone layer-safe refrigerants